|
The E.S.C.A.P.E. SystemTM |
|
(When
done with slide show close window to come back here)
|
How
UV-C lamps saved one company $58,000 From Electric Light & Power, February 2000 UVC
Light Beats Heat and Saves Energy in Dallas In 1998, with
56 days of temperatures 100 F or more, it's not surprising that utility bills
in Dallas ran 15 to 35 percent higher than typical summers. Again, during the
summer of 1999, record breaking heat forced building operators to crank up
their air conditioning systems-sometimes for 24 hours a day. But at the
headquarters of Central & South West Corp. (CSW) both this year and last,
building services technician David Lewis reports a significant decrease in
energy usage. Through the brutal 1998 summer, he says, they were able to cool
the near 500,000-sq. ft. building coasting along on a maximum of three,
300-ton chillers instead of the customary four. That amounts to an estimated 300+ kW reduction when factoring in the related equipment. How did CSW manage to defy the
statistics and save on chiller demand during record-breaking heat (Dallas's
second hottest summer ever)? Lewis attributes the reduced demand to the
February 1998 installation of UVC germicidal lights from Lewis installed the UVC
Emitters in all 20 of the building's air handling units, which ultimately made
further use of the increased cooling efficiency with their "variable
frequency drive" fan motors. "When we purchased the
product, we weren't even looking for energy savings: our motivation was indoor
air quality (IAQ)," stated Lewis. "Though we didn't have a specific
IAQ problem in the building, we always try to be environmentally
proactive." CSW is a global, diversified
company whose holdings include America's second largest utility system. The
company owns many electrical operating subsidiaries in Texas, Oklahoma, Ohio,
Missouri, Louisiana, and Arkansas. In fact, it was through one of these
subsidiaries -Public Service Company of Oklahoma (PSO) in Tulsa, Okla. - that
Lewis first became convinced of the benefits of UVC light. PSO had installed
the lights in 1996 and 1997 to eliminate a persistent mold and IAQ problem in
the majority of their HVAC systems. They found that, by bathing the coil and
drain pan areas from the downstream side with a newly developed UVC product;
they were able to eradicate the microbial growth and its related problems. The
lights also all but eliminated most of their customary coil cleaning
maintenance. "In following the PSO
example, we too have eliminated our four-times-per-year coil, drain pan and
plenum cleaning program and we no longer expose our maintenance people to the
biocidal agents and other cleaning chemicals required for these tasks. The
environmental benefit is a very big plus for CSW, not to mention a big cost
saver," said Lewis. "What we didn't anticipate was the rather
significant improvement in coil heat transfer efficiency, pressure drop and
the subsequent lower fan rpm. This all results from having our coils
continuously clean by the UVC lights. It also translates into a big power
consumption reduction." Lewis estimated that the
improvement had yielded a conservative 28 percent reduction in total A/C
system energy usage. This is mostly based on an energy cost of $0.054/kWh and
the 300+kWh savings over the 1998 summer's 3,600 operating hours (five
months), which likely exceeded $58,300. From that alone, the UVC light
system paid for itself in less than five months. "So when the energy
savings are added to the maintenance savings and IAQ proactively, they are all
proving significant. What's more, we are happy to see similar savings this
year," said Lewis. "Those who utilize variable frequency drives (VFDs)
on their fans, etc., will quickly see the promised energy savings once the
lights have cleaned their coils. Those considering VFDs may have more
incentive now to use them. Constant speed fan users will at least need to
check their damper settings, but many will be able to shave back to the
original design rpm for substantial energy savings." Lewis also noted that coils have remained free of mold and organic buildup for nearly a year and a half without any chemical cleaning or biocidal treatment. "We regularly test samples taken from coil surfaces as well as our condensate water, and these samples repeatedly come back clean, so we're confident that the lights are performing the desired germicidal function too." CSW maintenance crews
installed a total of 170 UVC light fixtures in the building's air handlers. A
radiometer is used at each air handler to measure the UVC output of the
lights. When that outputs falls below the specified level, the bulbs or
"Emitter tubes" will simply be replaced. "We're told that an
annual change out cycle is typical, but we are just now changing them after
almost 17 months of bulb life," Lewis reported. He also expects that the
UVC device will prolong the useful life of the building's older air handler
through cleaner, more efficient operation. "Coil replacement looks like
it's still a long way off, if ever." Half of the facility is 27 years old
and still equipped with the original air handling units. They were retrofitted
with VFDs in the late 1980s. The newer half of the building was constructed
about seven years ago with VFDs installed. With the PSO subsidiary coming
up on four years' experience with the UVC lights, facility supervisor Tom
McKain also reported significant maintenance and energy benefits. "These lights have the
ability to restore a marginally-performing air handler to peak
efficiency-bringing it back, essentially, to "as new"
condition," said McKain. "Once our coils were free of residue, we
were able to rebalance all of our air handling units and reduce fan speed to a
lower rpm. Due to this increase in efficiency, we estimate that the lights
paid for themselves in about six months of less-much faster than we'd
anticipated. And we haven't had to clean our coils, drain pans and plenums
since 1996." Tulsa, like Dallas, experienced record-breaking heat last summer, yet the PSO facility-like its parent company in Dallas-was able to reduce chiller demand also, cutting back from two chillers to one. "The UVC lights have performed beyond our expectations in all regards," McKain concluded. Call: Richard Fix 1-888-218-1146 Email: info@TheEscapeSystem.com
|